Alarms
Overview
Comms
Plant
High Service
Towers
Booster
Chemical
Remotes
Callout
Annunciation

Alarms

Live alarm state from the plant controllers. Display only — no callouts configured yet.

This page annunciates what the PLCs already decide. It does not write to any controller and does not place phone calls. Fourteen alarms are inhibited at the controller and will never appear here until those inhibits are cleared with operators.
ALL CONFIGURED ALARMS
StationAlarmTypeState
Process

System Overview

Raw water through the plant to storage and distribution.

Site

Station Health

Communication status for all twelve stations.

Treatment

Plant

Turbidity, clearwell levels, raw water.

Distribution

High Service

High service pumps and discharge.

Storage

Towers

Country Club and Idaho tower levels. Each shows the direct RTU read and the copy that arrives at PLC_WT01 by MSG — a divergence between them means one is stale.

Distribution

Booster Pump Station

11th Street standpipe and tower, booster pumps, chlorine.

Chemical

Analyzers

LASCTL is the source of truth for all chemical values.

Remote Sites

Remotes

Fort Cobb and Anadarko.

Alarm Callout

Callout List

Numbers are called in order, 1 first. Each rings 90 seconds on the first pass and 60 after, then the next number is tried. When the list is exhausted the cascade waits 2 minutes and starts again, and it keeps going until someone presses 1 or the alarm clears.

Call Order loading…

US numbers only. Type any format — (405) 555-1234 or 4055551234 — it is stored as +14055551234. Leave a slot blank to skip it.

Test the Callout Chain

This places a real phone call to one number from the list — whichever slot you pick. It exercises the whole chain: the call, the spoken message, and press-1 acknowledgment.

Answer and press 1 to confirm acknowledgment works. Nobody else is called, so it is safe to leave it unanswered.

Recorded in the alarm log against the signed-in user. This does not test escalation — only the slot you choose is rung.

ALARMS— none active —